Seri recloser otomatis CJ53RAi minangka unit kontrol kompak kanthi jembar mung 18MM, bisa diadaptasi karo pemutus sirkuit miniatur ing pasar.
| Model | Pemutus Sirkuit | ||||||||
| MCB | RCD (Remote Kontrol) | RCBO | |||||||
| 1P/2P | 3P/4P | 2P | 4P | 1P | 2P | 3P | 3P+N | 4P | |
| CJ53RAi-1-AC | √ | √ | √ | √ | |||||
| CJ53RAi-2-AC | √ | √ | √ | √ | √ | ||||
| CJ53RAix-1-AC | √ | √ | √ | √ | |||||
| CJ53RAix-2-AC | √ | √ | √ | √ | √ | ||||
| CJ53RAi-1-DC | √ | √ | √ | √ | |||||
| CJ53RAi-2-DC | √ | √ | √ | √ | √ | ||||
| CJ53RAix-1-DC | √ | √ | √ | √ | |||||
| CJ53RAix-2-DC | √ | √ | √ | √ | √ | ||||
| Karakteristik Listrik | |||
| Standar | EN 50557 | ||
| Sistem Distribusi Daya | TT – TN – S | ||
| Tegangan sing Dirating (Ue) | (V) | 230 AC (1) | |
| Tegangan Minimal (Ue Minimal) | (V) | 85% Ue | |
| Tegangan Rated Maks (Ue Maks) | (V) | 110% Ue | |
| Tegangan Isolasi sing Dirating (Ui) | (V) | 500 | |
| Kekuwatan Diaelektrik | (V) | 2500 AC sajrone 1 menit | |
| Tegangan Tahan Nilai (Uimp) | 4 | ||
| Kategori Tegangan Luwih | III | ||
| Frekuensi sing Dirating | (Hz) | 50 | |
| Kapasitas Pemecahan Bocoran Tanah (I△m) | (A) | I△c saka Breaker sing gegandhengan | |
| Arus Sirkuit Pendek Sisa sing Dirating (I△c) | (A) | I△m saka Pemutus sing gegandhengan | |
| Wong Polandia | 2 | 4 | |
| Tipe MCB | 1P – 2P – 3P – 4P | ||
| Tipe RCCB | AC – A – A[IR] – A[S] | ||
| Tipe RCBO | |||
| Arus Terukur (In) | (A) | 25 – 40 – 63 – 80 – 100 | |
| Arus Sisa Terukur (I△n) | (mA) | 30 – 100 – 300 – 500 | |
| Resistensi non-operasi sing dirating antarane komponen listrik lan lemah | (kΩ) | 8 (30mA) – 2,5 (100/300/500mA) | |
| Resistensi kerja sing dirating antarane bagean aktif lan bumi | (kΩ) | 16 (30mA) – 5 (100/300/500mA) | |
| Ing mundhut daya | (W) | Kehilangan daya saka pemutus sirkuit sing gegandhengan | |
| Daya Statis | (VA) | 1 | 1 |
| Daya nutup maneh otomatis | (VA) | 20 | 20 |
| Karakteristik Mekanik | |||
| Jembaré Modul DIN | 1 | 1 | |
| Interval Wektu Penutupan Ulang | (s) | 10 – 60 – 300 | |
| Frekuensi Operasi Maks. | (operasi/jam) | 30 | |
| Daya tahan mekanik maksimal (jumlah total operasi) | 10000 | ||
| Siklus Penutupan Otomatis Maks. | 60 | ||
| Nomer wektu reset counter Recopper terus-terusan operasi | (s) | 3 | |
| Bagian Terminal saka Pemutus | (mm²) | Kabel Lunak: ≤ 1×35 – ≤ 2×16 – ≤ 1×16+2×10 | |
| Torsi pengencangan sing dirating pemutus sirkuit | (Nm) | 3 (IDP) – 2 (IDP NA) | |
| Lokasi instalasi | Apa wae | ||
| Tingkat Proteksi Pemutus Sirkuit | IP20 () – IP40 () | ||
| Karakteristik Lingkungan | |||
| Tingkat Polusi | 2 | ||
| Suhu Kerja | (°C) | -25 +60 | -25 +60 |
| Suhu Panyimpenan | (°C) | -40 +70 | |
| Kelembapan Relatif | 55°C – Kiri Kanan 95% | ||
| Karakteristik Kontak Bantu | |||
| Bantuan | Ya | Ya | |
| Jinis Kontak | - | Relay Elektronik | |
| Tegangan sing Dirating | (V) | - | 5-230 AC/DC |
| Arus sing Dirating | (A) | - | 0.6 (min) -1 (maks) |
| Frekuensi | (Hz) | - | 50 |
| Gunakake kategori | - | AC12 | |
| Mode Operasi | - | Sinyal NO\NC\ Posisi Gagang | |
| Sambungan Kabel | (mm²) | - | ≤2.5 |
| Torsi Pengencangan sing Dirating | (Nm) | - | 0.4 |
| Fungsi Tutup Maneh Otomatis | |||
| Tutup Maneh Otomatis Nalika Gangguan Listrik Mati | √ | √ | |
| Tes Patahan Bumi | |||
| Tes Kebocoran Tanah | |||
| Nutup Manèh Stop Nalika Ana Kasalahan | √ | √ | |
| Sinyal Penutupan Manèh | |||
| Indikator Sinyal Gangguan | √ | √ | |
| Fungsi Otomatis/Manual | √ | √ | |
| Kontak Bantu kanggo Operasi Jarak Jauh | |||
| Proteksi Listrik Internal | PTC | PTC | |