| Tipe | 3P | SD16R | SD20R | SD25R | SD32R | SD40R | SD63R | SD80R | SD80HR | SD100R | SD125R |
| 4P | |||||||||||
| Arus pemanasan sing disepakati (≤40°C) | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 100A | 125A | |
| Operasional sing dirating IEC arus Ie AC-21A/B (≤690V) | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | |
| Arus operasional sing dirating IEC Yaiku AC-22A/B | 415V | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A |
| 500V | |||||||||||
| 690V | 32A/40A | 40A/63A | 63A/80A | 63A/80A | 80A/100A | 100A/125A | |||||
| Arus operasional sing dirating IEC Yaiku AC-23A/B | 415V | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A |
| 500V | 25A/25A | 63A/63A | 80A/100A | 100A/100A | |||||||
| 690V | 40A/40A | 63A/63A | 63A/63A | ||||||||
| Arus operasional sing dirating IEC Ie DC-21B | 110VDC | 16A(1) | 20A(1) | 25A(1) | 32A(1) | 40A(1) | 63A(1) | 80A(1) | 100A(1) | 100A(1) | 125A(1) |
| 250VDC | 16A(2) | 20A(2) | 25A(2) | 32A(2) | 40A(2) | 63A(2) | 80A(2) | 100A(2) | 100A(2) | 125A(2) | |
| 400VDC | 16A(3) | 20A(3) | 25A(3) | 25A(3) | 40A(3) | 63A(3) | |||||
| Daya operasional sing dirating IEC (3 Phse) AC-23A/B | 415V | 7.5KW | 9KW | 11KW | 15KW | 18.5KW | 30KW | 37KW | 45KW | 55KW | |
| 500V | |||||||||||
| 690V | 11KW | 15KW | |||||||||
| Arus tahan hubung singkat saka proteksi sekering (nilai sing diarepake kA rms) | |||||||||||
| Kelas sekering | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 125A | ||
| Dirating kondisional arus hubung singkat | 50kA | 25kA | |||||||||
| Korsleting tahan arus saka pemutus sirkuit kanggo proteksi, pemutus sirkuit apa wae sing bisa trip sajrone 0,3 detik | |||||||||||
| Dirating wektu cendhak tahan arus | 2,5 kA | 3kA | 5kA | ||||||||
| Kinerja sirkuit cendhak (tanpa perlindungan) | |||||||||||
| Arus tahan wektu cendhak sing dirating | 1.26kA | 1.5kA | 2.75kA | ||||||||
| Kapasitas nggawe sirkuit cendhak sing dirating | 1.8kA | 2.1kA | 3.9kA | ||||||||
| Area lintas terminal | 1.5~16mm² | 2.5-35mm² | 10~70mm² | ||||||||
| Tegangan insulasi sing dirating Ui | 800V | ||||||||||
| Tegangan tahan impuls sing dirating Uimp | 8kV | ||||||||||
| Daya Tahan Mekanik | 100000 | ||||||||||
| Suhu Sekitar | Operasi -25°C…+55°C / Panyimpenan -40°C…+70°C | ||||||||||
| (1) Saben kutub digunakake minangka positif lan negatif (2) Telung kutub digunakake kanthi seri kanthi kutub positif lan negatif, sing loro kutub kasebut seri, lan liyane negatif (3) Papat kutub digunakake kanthi seri kanthi kutub positif lan negatif | |||||||||||