CJ:Kode perusahaan
M: Pemutus sirkuit kasus cetakan
1: Desain No
□: Arus sing dirating saka pigura
□: Kode karakteristik kapasitas pemecah/S nuduhake jinis standar (S bisa diilangi) H nuduhake jinis sing luwih dhuwur
Cathetan: Ana patang jinis kutub netral (kutub N) kanggo produk patang fase. Kutub netral tipe A ora dilengkapi elemen tripping arus berlebih, tansah diuripake, lan ora diuripake utawa dipateni bebarengan karo telung kutub liyane.
Kutub netral tipe B ora dilengkapi elemen tripping arus berlebih, lan diuripake utawa dipateni bebarengan karo telung kutub liyane (kutub netral diuripake sadurunge dipateni). Kutub netral tipe C dilengkapi elemen tripping arus berlebih, lan diuripake utawa dipateni bebarengan karo telung kutub liyane (kutub netral diuripake sadurunge dipateni). Kutub netral tipe D dilengkapi elemen tripping arus berlebih, mesthi diuripake lan ora diuripake utawa dipateni bebarengan karo telung kutub liyane.
| Jeneng aksesoris | Rilis elektronik | Pelepasan senyawa | ||||||
| Kontak bantu, ing ngisor voltase rilis, kontak alam | 287 | 378 | ||||||
| Rong set kontak bantu, kontak alarm | 268 | 368 | ||||||
| Pelepasan shunt, kontak alarm, kontak bantu | 238 | 348 | ||||||
| Ing ngisor voltase rilis, kontak alarm | 248 | 338 | ||||||
| Kontak bantu kontak alarm | 228 | 328 | ||||||
| Kontak alarm pelepasan shunt | 218 | 318 | ||||||
| Kontak bantu sing ora bisa dilepasake voltasene | 270 | 370 | ||||||
| Rong set kontak bantu | 260 | 360 | ||||||
| Pelepasan shunt ing ngisor voltase | 250 | 350 | ||||||
| Kontak bantu pelepasan shunt | 240 | 340 | ||||||
| Pelepasan voltase kurang | 230 | 330 | ||||||
| Kontak bantu | 220 | 320 | ||||||
| Pelepasan shunt | 210 | 310 | ||||||
| Kontak alarm | 208 | 308 | ||||||
| Ora ana aksesoris | 200 | 300 | ||||||
| 1 Nilai sing dirating saka pemutus sirkuit | ||||||||
| Model | Imax (A) | Spesifikasi (A) | Tegangan Operasi sing Dirating (V) | Tegangan Isolasi sing Dirating (V) | Icu (kA) | Ic (kA) | Cacahing Kutub (P) | Jarak Lengkung (mm) |
| CJMM1-63S | 63 | 6,10,16,20 25,32,40, 50,63 | 400 | 500 | 10* | 5* | 3 | ≤50 |
| CJMM1-63H | 63 | 400 | 500 | 15* | 10* | 3,4 | ||
| CJMM1-100S | 100 | 16,20,25,32 40,50,63, 80.100 | 690 | 800 | 35/10 | 22/5 | 3 | ≤50 |
| CJMM1-100H | 100 | 400 | 800 | 50 | 35 | 2,3,4 | ||
| CJMM1-225S | 225 | 100,125, 160,180, 200.225 | 690 | 800 | 35/10 | 25/5 | 3 | ≤50 |
| CJMM1-225H | 225 | 400 | 800 | 50 | 35 | 2,3,4 | ||
| CJMM1-400S | 400 | 225.250, 315.350, 400 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
| CJMM1-400H | 400 | 400 | 800 | 65 | 35 | 3 | ||
| CJMM1-630S | 630 | 400.500, 630 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
| CJMM1-630H | 630 | 400 | 800 | 65 | 45 | 3 | ||
| Cathetan: Nalika parameter uji kanggo 400V, 6A tanpa pemanasan dibebasake | ||||||||
| 2 Karakteristik operasi pemutus wektu terbalik nalika saben kutub pelepasan arus berlebih kanggo distribusi daya diuripake bebarengan | ||||||||
| Item saka Arus Tes (I/In) | Wilayah wektu uji coba | Kahanan awal | ||||||
| Arus non-tripping 1.05In | 2 jam(n>63A),1 jam(n<63A) | Kahanan adhem | ||||||
| Arus trip 1.3In | 2 jam(n>63A),1 jam(n<63A) | Langsung wae sawise tes No. 1 | ||||||
| 3 Karakteristik operasi pemecahan wektu terbalik nalika saben kutub over- Arus sing metu kanggo proteksi motor uga diuripake bebarengan. | ||||||||
| Nyetel Wektu Konvensional Saiki Kahanan Awal | Cathetan | |||||||
| 1.0Ing | >2 jam | Kahanan Adhem | ||||||
| 1.2In | ≤2 jam | Ditindakake langsung sawise tes No.1 | ||||||
| 1.5In | ≤4 menit | Kahanan Adhem | 10≤Ing≤225 | |||||
| ≤8 menit | Kahanan Adhem | 225≤Ing≤630 | ||||||
| 7.2In | 4s≤T≤10s | Kahanan Adhem | 10≤Ing≤225 | |||||
| 6s≤T≤20s | Kahanan Adhem | 225≤Ing≤630 | ||||||
| 4 Karakteristik operasi sesaat saka pemutus sirkuit kanggo distribusi daya kudu disetel minangka 10in + 20%, lan karakteristik pemutus sirkuit kanggo proteksi motor kudu disetel minangka 12ln ± 20% |
CJMM1-63, 100, 225, Ukuran Garis Besar lan Pemasangan (Sambungan papan ngarep)
| Ukuran (mm) | Kode Model | |||||||
| CJMM1-63S | CJMM1-63H | CJMM1-63S | CJMM1-100S | CJMM1-100H | CJMM1-225S | CJMM1-225 | ||
| Ukuran Garis Besar | C | 85.0 | 85.0 | 88.0 | 88.0 | 102.0 | 102.0 | |
| E | 50.0 | 50.0 | 51.0 | 51.0 | 60.0 | 52.0 | ||
| F | 23.0 | 23.0 | 23.0 | 22.5 | 25.0 | 23.5 | ||
| G | 14.0 | 14.0 | 17.5 | 17.5 | 17.0 | 17.0 | ||
| G1 | 6.5 | 6.5 | 6.5 | 6.5 | 11.5 | 11.5 | ||
| H | 73.0 | 81.0 | 68.0 | 86.0 | 88.0 | 103.0 | ||
| H1 | 90.0 | 98.5 | 86.0 | 104.0 | 110.0 | 127.0 | ||
| H2 | 18.5 | 27.0 | 24.0 | 24.0 | 24.0 | 24.0 | ||
| H3 | 4.0 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | ||
| H4 | 7.0 | 7.0 | 7.0 | 7.0 | 5.0 | 5.0 | ||
| L | 135.0 | 135.0 | 150.0 | 150.0 | 165.0 | 165.0 | ||
| L1 | 170.0 | 173.0 | 225.0 | 225.0 | 360.0 | 360.0 | ||
| L2 | 117.0 | 117.0 | 136.0 | 136.0 | 144.0 | 144.0 | ||
| W | 78.0 | 78.0 | 91.0 | 91.0 | 106.0 | 106.0 | ||
| W1 | 25.0 | 25.0 | 30.0 | 30.0 | 35.0 | 35.0 | ||
| W2 | - | 100.0 | - | 120.0 | - | 142.0 | ||
| W3 | - | - | 65.0 | 65.0 | 75.0 | 75.0 | ||
| Ukuran Instalasi | A | 25.0 | 25.0 | 30.0 | 30.0 | 35.0 | 35.0 | |
| B | 117.0 | 117.0 | 128.0 | 128.0 | 125.0 | 125.0 | ||
| od | 3.5 | 3.5 | 4.5 | 4.5 | 5.5 | 5.5 | ||
CJMM1-400,630,800, Ukuran Garis Besar lan Instalasi (Sambungan papan ngarep)
| Ukuran (mm) | Kode Model | |||||||
| CJMM1-400S | CJMM1-630S | |||||||
| Ukuran Garis Besar | C | 127 | 134 | |||||
| C1 | 173 | 184 | ||||||
| E | 89 | 89 | ||||||
| F | 65 | 65 | ||||||
| G | 26 | 29 | ||||||
| G1 | 13.5 | 14 | ||||||
| H | 107 | 111 | ||||||
| H1 | 150 | 162 | ||||||
| H2 | 39 | 44 | ||||||
| H3 | 6 | 6.5 | ||||||
| H4 | 5 | 7.5 | ||||||
| H5 | 4.5 | 4.5 | ||||||
| L | 257 | 271 | ||||||
| L1 | 465 | 475 | ||||||
| L2 | 225 | 234 | ||||||
| W | 150 | 183 | ||||||
| W1 | 48 | 58 | ||||||
| W2 | 198 | 240 | ||||||
| A | 44 | 58 | ||||||
| Ukuran Instalasi | A1 | 48 | 58 | |||||
| B | 194 | 200 | ||||||
| Od | 8 | 7 | ||||||
Diagram Pemotongan Sambungan Papan Mburi Colokke
| Ukuran (mm) | Kode Model | ||||||
| CJMM1-63S CJMM1-63H | CJMM1-100S CJMM1-100H | CJMM1-225S CJMM1-225H | CJMM1-400S | CJMM1-400H | CJMM1-630S CJMM1-630H | ||
| Ukuran Tipe Plug-in Koneksi Backboard | A | 25 | 30 | 35 | 44 | 44 | 58 |
| od | 3.5 | 4.5*6 bolongan jero | 3.3 | 7 | 7 | 7 | |
| od1 | - | - | - | 12.5 | 12.5 | 16.5 | |
| od2 | 6 | 8 | 8 | 8.5 | 9 | 8.5 | |
| oD | 8 | 24 | 26 | 31 | 33 | 37 | |
| oD1 | 8 | 16 | 20 | 33 | 37 | 37 | |
| H6 | 44 | 68 | 66 | 60 | 65 | 65 | |
| H7 | 66 | 108 | 110 | 120 | 120 | 125 | |
| H8 | 28 | 51 | 51 | 61 | 60 | 60 | |
| H9 | 38 | 65.5 | 72 | - | 83.5 | 93 | |
| H10 | 44 | 78 | 91 | 99 | 106.5 | 112 | |
| H11 | 8.5 | 17.5 | 17.5 | 22 | 21 | 21 | |
| L2 | 117 | 136 | 144 | 225 | 225 | 234 | |
| L3 | 117 | 108 | 124 | 194 | 194 | 200 | |
| L4 | 97 | 95 | 9 | 165 | 163 | 165 | |
| L5 | 138 | 180 | 190 | 285 | 285 | 302 | |
| L6 | 80 | 95 | 110 | 145 | 155 | 185 | |
| M | M6 | M8 | M10 | - | - | - | |
| K | 50.2 | 60 | 70 | 60 | 60 | 100 | |
| J | 60.7 | 62 | 54 | 129 | 129 | 123 | |
| M1 | M5 | M8 | M8 | M10 | M10 | M12 | |
| W1 | 25 | 35 | 35 | 44 | 44 | 58 | |
Ing MCCB, kapasitas pemutus sirkuit cendhak sing dirating nuduhake kapasitas pemutus ing kahanan sing ditemtokake. Sawise prosedur uji sing ditemtokake, perlu ditimbang manawa pemutus sirkuit terus nggawa arus sing dirating. Kanggo nyukupi kabutuhan pangguna sing beda-beda, akeh produsen pemutus sirkuit saiki mbagi kapasitas pemutus sirkuit cendhak saka arus rating shell sing padha dadi tingkat sing beda-beda, lan pangguna bisa milih pemutus sirkuit sing cocog miturut kabutuhane saka pemutus sirkuit arus minimal nganti maksimum. Pemutus sirkuit iki umum banget lan ditemokake ing meh kabeh bangunan utawa struktur saengga asring dianggep remeh. Nanging, pemutus sirkuit iki nduweni peran penting ing sistem jaringan listrik lan kudu dijaga supaya tetep cocog karo standar keamanan paling anyar.
MCCB nyedhiyakake respon cepet kanggo arus gangguan hubung singkat, adhedhasar prinsip elektromagnetisme. MCCB ngemot koil solenoid sing ngasilake medan elektromagnetik cilik nalika arus ngliwati MCCB. MCCB nggunakake piranti sensitif suhu (elemen termal) kanthi piranti elektromagnetik sensitif arus (elemen magnetik) kanggo nyedhiyakake mekanisme trip (magnetik termal) kanggo tujuan proteksi termal lan isolasi. Sajrone operasi normal utawa kahanan normal, medan elektromagnetik sing diasilake dening koil solenoid bisa diabaikan. Nanging, nalika ana gangguan hubung singkat ing sirkuit, arus gedhe wiwit mili liwat solenoid lan, akibate, medan elektromagnetik sing kuwat digawe sing narik bilah trip lan mbukak kontak.