| Standar | IEC60947-2 |
| Pole No | 1P, 2P, 3P, 4P |
| Tegangan Rated | 1P:250V 2P:500V 3P:800V 4P:1000V |
| Dirating Saiki Ing (A) | 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63, |
| Tripping Curve | B, C |
| Kapasitas putus sirkuit cendhak sing dirating | 10kA |
| Rated impuls tahan voltase | 6.2KV |
| Daya tahan elektro-mekanik | 10000 |
| Terminal sekrup | M5 |
| Dirating torsi | 2.0Nm |
| Prosedur tes | Jinis | Tes Saiki | Negara wiwitan | Tripping utawa Non-tripping Watesan Wektu | Hasil sing Dikarepake | Tetembungane |
| A | B,C | 1.05 Ing | kadhemen | t≥1h(In≤63A) t≥2h(In>63A) | ora tripping | |
| B | B,C | 1.3 Ing | sawise tes A | t<1h(In≤63A) t<2h(In>63A) | kesandung | Saiki ing 5s ing th nambah stabilitas |
| C | B,C | 2 Ing | kadhemen | 10s20s63A) | kesandung | |
| D | B | 4 Ing | kadhemen | t≤0.2s | ora tripping | Nguripake ngalih tambahan kanggo |
| E | C | 8 Ing | nutup saiki | |||
| D | 6 Ing | kadhemen | t<0.2s | kesandung | ||
| B | 12 Ing |