| Prosedur uji coba | Tipe | Arus Uji | Kahanan Awal | Watesan Wektu Tripping utawa Ora Tripping | Asil sing diarepake | Cathetan |
| A | B,C,D | 1.13 Ing | adhem | t≤1 jam | Ora kena kesandhung | |
| B | B,C,D | 1.45In | Sawise Tes A | t<1 jam | Kesandung | Arus terus mundhak nganti nilai sing ditemtokake sajrone 5 detik |
| C | B,C,D | 2.55In | adhem | 1s | Kesandung | | |
| D | B | 3In | adhem | t≤0.1s | Ora kena kesandhung | Uripake saklar bantu kanggo nutup arus |
| C | 5In | |||||
| D | 10In | |||||
| E | B | 5In | adhem | t <0.1s | Kesandung | Uripake saklar bantu kanggo nutup arus |
| C | 10In | |||||
| D | 20In |
| Tipe | Ing/A | I△n/A | Arus Sisa (I△) Cocog karo Wektu Pecah Sabanjure (S) | ||||
| Tipe AC | apa wae nilai | apa wae nilai | 1ln | 2In | 5In | 5A, 10A, 20A, 50A 100A, 200A, 500A | |
| Tipe A | >0.01 | 1.4In | 2.8In | 7In | |||
| 0.3 | 0.15 | 0.04 | 0.04 | Wektu Istirahat Maksimum | |||
| RCBO tipe umum sing arus IΔn-e 0,03mA utawa kurang bisa nggunakake 0,25A tinimbang 5IΔn. | |||||||
| Indikator arus gangguan | YA |
| Tingkat perlindungan | IP20 |
| Suhu sekitar | -25°C~+40°C lan rata-rata sajrone periode 24 jam ora ngluwihi +35°C |
| Suhu panyimpenan | -25°C~+70°C |
| Ukuran terminal ndhuwur/ngisor kanggo kabel | 25mm2 |
| Torsi pengencangan | 2.5Nm |
| Koneksi | Ndhuwur lan ngisor |
| Jinis sambungan terminal | Kabel/busbar tipe-U/busbar tipe-Pin |
| Pemasangan | Ing rel DlN 35mm nganggo piranti klip cepet |