Standar | IEC/EN 60898-1 | ||||
Rated Saiki | 6A,10A,16A,20A,25A,32A,40A,50A,63A | ||||
Tegangan Rated | 230/400VAC(240/415) | ||||
Frekuensi Rated | 50/60Hz | ||||
Jumlah Pole | 1P,2P,3P,4P(1P+N,3P+N) | ||||
Ukuran modul | 18 mm | ||||
Tipe kurva | Tipe B, C, D | ||||
Kapasitas breaking | 4500A, 6000A | ||||
Suhu operasi optimal | -5ºC nganti 40ºC | ||||
Torsi Pengetatan Terminal | 5N-m | ||||
Kapasitas Terminal (ndhuwur) | 25 mm² | ||||
Kapasitas Terminal (ngisor) | 25 mm² | ||||
Daya tahan elektro-mekanik | 4000 siklus | ||||
Pemasangan | DinRail 35mm Kab | ||||
Busbar sing cocog | PIN Busbar |
Tes | Tipe Tripping | Tes Saiki | Negara wiwitan | Wektu tripping utawa Non-tripping Time Provider | |
a | Wektu tundha | 1.13 Ing | kadhemen | t≤1h(Ing≤63A) | Ora Tripping |
t≤2h(ln>63A) | |||||
b | Wektu tundha | 1.45 Ing | Sawise tes a | t<1h(Ing≤63A) | Kesandung |
t<2h(Ing>63A) | |||||
c | Wektu tundha | 2.55 Ing | kadhemen | 10s | Kesandung |
20s63A) | |||||
d | kurva B | 3 Ing | kadhemen | t≤0.1s | Ora Tripping |
kurva C | 5 Ing | kadhemen | t≤0.1s | Ora Tripping | |
D kurva | 10 Ing | kadhemen | t≤0.1s | Ora Tripping | |
e | kurva B | 5 Ing | kadhemen | t≤0.1s | Kesandung |
kurva C | 10 Ing | kadhemen | t≤0.1s | Kesandung | |
D kurva | 20 Ing | kadhemen | t≤0.1s | Kesandung |