Rating pemutus sirkuit
| Model | Rating pigura arus sing dirating Ing (mA) | Dirating saiki Ing (A) | Dirating nyambut gawe voltase (V) | Dirating Isolasi voltase (V) | Dirating paling apik korsleting pecah kapasitas Icu(kA) | Operasi sing dirating korsleting pecah kapasitas Ics (kA) | Nomer of tiang-tiang | Kilatan jarak (mm) |
| CJMM3-125S | 125 | 16, 20, 25, 32, 40,50,60,80, 100.125 | 400/415 | 1000 | 25 | 18 | 3P | ≤50 |
| CJMM3-125H | 125 | 35 | 25 | 3P | ||||
| CJMM3-250S | 250 | 100,125,160, 180,200,225, 250 | 400/690 | 800 | 35/10 | 25/5 | 2P, 3P, 4P | ≤50 |
| CJMM3-250S | 250 | 600 | 50 | 35 |
Karakteristik aksi pemutus wektu terbalik saka pelepasan arus luwih saka pemutus sirkuit distribusi nalika kabeh kutub dialiri energi ing wektu sing padha
| Tes jeneng saiki | Aku/Ing | Wektu sing wis ditemtokake | Kahanan wiwitan |
| Setuju ora ana arus sing tiba | 1.05 | 2 jam (Ing >63A), 1 jam (Ing ≤63A) | Kahanan adhem |
| Arus tripping sing disepakati | 1.3 | 2 jam (Ing >63A), 1 jam (Ing ≤63A) | Sanalika sawise tes urutan 1, wiwiti |
Karakteristik aksi pemutus wektu terbalik saka pelepasan arus luwih saka pemutus sirkuit kanggo proteksi motor nalika kabeh kutub diwenehi energi bebarengan
| Nyetel arus | Wektu sing wis ditemtokake | Kahanan wiwitan | Cathetan |
| 1.0Ing | >2 jam | Kahanan adhem | |
| 1.2In | ≤2 jam | Sanalika sawise tes urutan 1, wiwiti | |
| 1.5In | ≤4 menit | kahanan adhem | 10 ≤ Ing ≤ 250 |
| ≤8 menit | kahanan adhem | 250 ≤ Ing ≤ 630 | |
| 7.2In | 4s≤T≤10s | kahanan adhem | 10 ≤ Ing ≤ 250 |
| 6s≤T≤20s | kahanan adhem | 250 ≤ Ing ≤ 800 |
Karakteristik operasi sesaat saka pemutus sirkuit kanggo distribusi disetel dadi 10In±20%, lan karakteristik operasi sesaat saka pemutus sirkuit kanggo proteksi motor disetel dadi 12In±20%.