Standar | IEC/EN 60898-1 | ||||
Pole No | 1P, 1P+N, 2P, 3P, 3P+N, 4P | ||||
voltase dirating | AC 230V/400V | ||||
Rated Saiki (A) | 20A,25A,32A,40A,50A,63A,80A,100A,125A | ||||
Kurva tripping | C, D | ||||
Kapasitas hubung singkat (lcn) | 10000A | ||||
Kapasitas sirkuit hubung singkat (ICs) | 7500A | ||||
Frekuensi dirating | 50/60Hz | ||||
Rated impuls tahan voltase Uimp | 6 kv | ||||
Terminal sambungan | Terminal pilar kanthi clamp | ||||
Daya tahan elektro-mekanik | Ins100=10000:n125=8000 | ||||
Dhuwur Sambungan Terminal | 20 mm | ||||
Kapasitas sambungan | Konduktor fleksibel 35mm² | ||||
Konduktor kaku 50mm² | |||||
Instalasi | Ing rel DIN simetris 35mm | ||||
Pemasangan panel |
Tes | Tipe Tripping | Tes Saiki | Negara wiwitan | Wektu tripping utawa Non-tripping Time Provider | |
a | Wektu tundha | 1.05 Ing | kadhemen | t≤1h(Ing≤63A) t≤2h(ln>63A) | Ora Tripping |
b | Wektu tundha | 1.30 Ing | Sawise tes a | t<1h(Ing≤63A) t<2h(Ing>63A) | Kesandung |
c | Wektu tundha | 2 Ing | kadhemen | 10s 20s63A) | Kesandung |
d | Seketika | 8ln | kadhemen | t≤0.2s | Ora Tripping |
e | instan | 12 Ing | kadhemen | t<0.2s | Kesandung |
Nalika MCB kena arus liwat terus-terusan, jalur bimetal dadi panas lan mlengkung.Kancing elektromekanis dibebasake nalika MCB nyopot jalur bi-metallic.Nalika pangguna nyambungake clasp elektromekanis iki menyang mekanisme kerja, kontak pemutus microcircuit mbukak.Akibate, iku nimbulaké MCB kanggo ngalih mati lan siksa saiki mili.Pangguna kudu ngalih ing MCB kanggo mulihake aliran saiki.Piranti iki nglindhungi saka cacat sing disebabake arus kakehan, kakehan, lan sirkuit cendhak.